KINGSINE KFA310 Mini Handheld Protection Relay Tester

Kingsine KFA310 relay testing equipment has been designed with a compact interior, similar in size to an iPad, powered by batteries. This secondary injection test set weighs only 3.7 kg and offers 4x300V and 3x20A outputs. Its maximum current can reach 50A,  and the output power reaches 130VA.
 
Kingsine relay tester kit focuses on Maintenance and Testing of Distribution and Medium-L
ติดต่อสอบถาม

KFA310 Mini Handheld Protection Relay Tester

Product Feature:

1. Kingsine KFA310 protection relay testing equipment marks the world’s smallest protection relay tester with 7.0-inch LED touch screen. Easy to carry, iPad-sized, and weighing only 3.7 kg, it outputs up to 50A with high precision and can continuously output 3x10A conditions.

2. Extremely simple design for its internal structure, ensures high quality and reliability.

3. Innovative “Plug and Play” technology enables this mini handheld secondary injection test set to make after-sales service very easy and efficient, within 20 working days.

4. Main functions

 ▪ AC/DC test, Ramping, State Sequence, Harmonic, Distance, Overcurrent

 ▪ Oscillate Test: This secondary injection test set can be used for customizing superimposed oscillation waveform simulation testing.

 ▪ Frequency test (df/dt, ROCOF)

 ▪ 3-Phase standard Power source

 ▪ Energy meter calibration

 ▪ Double-device synchronous test (up to 6 current channels for differential test)

 ▪ 8 Channels Low-Level outputs (0 – 8Vrms)

5. With its high-precision output, this mini handheld secondary injection test set can be used as a standard source.

6. Stay ready for any test with our waterproof All-in-one Bag, designed for engineers to carry KFA series mini testers, cable packs, laptops, and tools—engineered for mobility.

Technical Parameters

AC Voltage Outputs
    22.5 VA max each@300V
    21 VA max each@200V
 Output Range & Power 4×300 V ac (L-N) 12.5 VA max each@100V
    7 VA max each@63.5V
    6.65 VA max each@57.7V
    1.1 VA max each@10V
Accuracy <0.015%Rd+0.005%Rg Typ.
<0.02%Rd+0.03%Rg Guar.
Resolution 0.001V
Distortion <0.05%Typ. / <0.1% Guar.
DC Offset <5mV Typ.
<60mV Guar
Ascends/Descent response <100us
DC Voltage Outputs
Source Channels 4
DC voltage output range 0~300 V (L-N)
DC voltage output power 22.5W Max
DC voltage accuracy <0.03%Rd+0.01Rg Typ.
<0.04%Rd+0.06Rg Guar.
Ascends/Descent response <100us
Resolution 1mV
AC current outputs
Source Channels 3
AC current output range 0~10A, L-N / (Can be optional as 0~20A)
0~20A, LL-N / (Can be optional as 0~40A)
0~30A, LLL-N / (Can be optional as 0~50A)
AC current output power(Max) 75VA Max for 10A L-N
130VA Max for 20A L-N/LLL-N
AC current output accuracy <0.015%Rd+0.01%Rg Typ.
<0.02%Rd+0.03%Rg Guar.
DC Offset <1mA Typ.
<2mA Guar
Distortion <0.05%Typ. / <0.1% Guar.
Ascends/Descent response <100us
Resolution 1mV
DC current outputs
Source Channels 1
DC current output range 0~10A, L-N
DC current output power 138W
DC current accuracy <0.03%Rd+0.01Rg Typ.
<0.04%Rd+0.06Rg Guar.
Resolution 1mA
AC frequency
Range sine signals DC, 10 ~ 1000Hz
Output accuracy ±5ppm
Resolution 0.001Hz
Phase
Output range -360°~360°
50Hz output accuracy ±0.1° Typ. / <0.2° Guar.
Resolution 0.001°
Auxiliary DC supply
Output range 12~350V
Output power 40W max
Accuracy <1%
Binary input and time accuracy
Binary input logarithm 4 pairs
Trigger mode Dry/Wet contact
Input voltage range 0 V~300Vdc
Timing accuracy < ±1ms @ 0.001~1s,
< ±0.1% @ >1s
Timing resolution 36us
Max time limit infinity
Binary output (Relay Contacts)
Binary output pairs 2 pairs(DO-1 and DO-2)
Type Potential free relay contacts,software controlled
Break capacity AC Vmax:380V(AC)/ Imax:8A/Pmax:2000VA
Break capacity DC Vmax:240V(DC)/ Imax:5A/Pmax:150W
Responce time ≤10 ms
Binary output (Fast eSSR)
Binary output pairs 2 pairs(DO-3 and DO-4)
Circuit Breaker Simulate Can be define as Open or Close status
Break capacity AC Vmax:250V(AC)/ Imax:0.5A
Break capacity DC Vmax:250V(DC)/ Imax:0.5A
Responce time <100us
Contact performance Open the dry contact output using opto-coupler relay, the on-resistance is ≤ 6Ω, and the shut-off withstand voltage is ≥DC300V
Time Synchronization (Time accuracy)
GPS / BD Yes, 5us
IRIG-B Yes, 5us
Power supply
Rated power supply 100 ~ 240Vac,1-phase
Enable input voltage 100~264Vac
Rated input frequency 50 Hz/60 Hz
Enable input frequency 47 Hz ~ 63Hz
Inbuilt Battery
Nominal volume 28.8V – 93.6Wh, (3250mAh)
Operating Temperature Charge: 0 to 45°C  (Ambient)
Discharge: -20 to 60°C  (Ambient)
Charge time (0-80%) 2h
Charge time (0-100%) 4h
Interface port
RJ45 Ethernet 1 port, 10/100M
USB USB3.0 x 1
Wifi Optional
Bluetooth Optional
Operation Control
Touch Screen & Host Control Yes, 7.0″ LCD
Basic PC software Optional
Advance PC software Optional
Other information
Weight 3.7kg
Dimensions(W x D x H) 288x185x95 (mm)
   Item    Standard    Optional
  Current output   3×10A   Upgrade to 3×20A
  Wifi    –   Optional support
  Bluetooth    –   Optional support
  Low-Level output    –   Optional support
  Energy Meter calibration    –   Optional support
  Basic PC software    Basic Modules   –

Low level outputs(Optional):

Number of outputs   8
Setting ranges 0~8Vrms
Max. output current Rating 2mA, 10mA transient max.
Accuracy (0.01~0.8 Vrms):
<0.05% Typ. / <0.1% Guar.
(0.8~8 Vrms):
<0.02% Typ. / <0.05% Guar.
Resolution 250 μV
Distortion (THD+N) < 0.05% Typ. / <0.1% Guar.
Connection interface Phoenix terminal

Energy Meter Calibration (Optional)

Sensor Usage Mechanical meters / Electronic meters
Sensor Output High lever:>4.5V, Low level:<0.2V
Pulse Input High lever:>4.5V, Low level:<0.2V
Pulse Range 500KHz pulse input Max.
Pulse Output 1 Transistor output, Open-collector, 5Vdc/5mA