K3063i Universal Protection Relay Test Set

High precision and powerful 6-phase relay test set and commissioning tool;
Power & Accuracy in one single PACKAGE, 6x35A, 4x310V analog outputs;
The ever-expanding test library templates;
ติดต่อสอบถาม

K3063i Universal Protection Relay Test Set

Basic Functions
  • Universal Relay Test Applications
  • 10 Channels (6x35A & 4x310V) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 60x harmonics.
  • Variable battery simulator, DC 0-350V, 140Watts max.
  • Transient play back up to 3KHz
  • Fully function KRT software testing modules
  • Graphical test modules and templates for testing of various relays
  • Quick relay testing facility in Manual mode
  • Shot/Search/Check, Point & Click testing
  • RIO/XRIO import & export facility
  • Switch on to fault test(SOTF)
  • Power system model for dynamic testing
  • Online Vector display
  • Automatic test results assume
  • Automatic test report creation
  • Inbuilt GPS sync end-to-end testing
  • Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection
  •  3-Years guarantee of free repair and life-long maintenance
  • Lightweight, <19.5Kg
  • Free software upgrade 
Advance Feature
  • Energy meter calibration (Mechanical & Electronic meters)
 
Type of relays can be tested:
   Items    ANSI® No.
   Distance protection relay    21
   Synchronising or synchronism-check relays    25
   Undervoltage relays    27
   Directional Power relays    32
   Undercurrent or underpower relays    37
   Negative sequence overcurrent relays    46
   Overcurrent/ground fault relays    50
   Inverse time overcurrent/ground fault relays    51
   Power factor relays    55
   Overvoltage relays    59
   Voltage or current balance relays    60
   Directional overcurrent relays    67
   Directional ground fault relays    67N
   DC overcurrent relays    76
   Phase-angle measuring or out-of-step protection relays    78
   Automatic reclosing devices    79
   Frequency relays    81
   Motor overload protection relays    86
   Differential protection relays    87
   Directional voltage relays    91
   Voltage and power directional relays    92
   Tripping relays    94
   Voltage regulating relays  
   Overimpedance relays, Z>  
   Underimpedance relays, Z  
   Time-delay relays  

 

Voltage Outputs
Output Range & Power 4×310 V ac (L-N) 124 VA max each
3×350 V dc (L-N) 140 W max each
Accuracy ±2mV @ <2V ac
<0.015%Rd+0.005Rg Typ. @ 2~310V ac
<0.04%Rd+0.01Rg Guar. @ 2~310V ac
±10mV @ <5V dc
±0.5% @ ≥5V dc
Voltage Range Range I : 30V
Range II : 310V
Automatic Range
DC Offset <10mV Typ./ <60mV Guar
Resolution 1mV
Distortion <0.015%Typ. / <0.05% Guar.
Current Outputs
Output Range & Power 6×35A ac (L-N) 450 VA max each
3×70A ac (2L-N) 850 VA max each
1×100A ac (6L-N) 1200 VA max
3×20A dc (L-N) 300W max each
Accuracy ±1mA @ <0.5A ac
<0.02%Rd+0.01Rg Typ. @ 0.5A~35A ac
<0.05%Rd+0.02Rg Guar. @ 0.5A~35A ac
±5mA @ <1A dc
±0.5% @ ≥1A dc
Current Range Range I: 3A
Range II: 35A
Automatic Range
DC Offset <3mA Typ./ <10mA Guar
Resolution 1mA
Distortion <0.025%Typ. / <0.07% Guar.
Frequency & Phase Angle
Frequency Range DC~1KHz, 3KHz transient
Frequency Accuracy ±0.5ppm
Frequency Resolution 0.001 Hz
Phase Range -360°~360°
Phase Accuracy <0.02° Typ. / <0.1° Guar. 50/60Hz
Phase Resolution 0.001°
Aux. DC Voltage Source (Battery simulator)
Range 0~350V @ 140W max
Accuracy 0.5%Rg Guar.
Binary Input
Quantity 8pairs
Type wet/dry, up to 300Vdc max input
Time resolution 10us
Sampling Rate 10KHz
Debounce time 0~25ms (Software Controlled)
Time range Infinite
Time errors ±1ms @ ≤1s, ±0.1% @ >1s
Galvanic isolation Isolated each pairs
Binary Output (Relay Type)
Quantity 4pairs
Type Potential free relay contacts, software controlled
Break Capacity AC Vmax: 400Vac / Imax:8A / Pmax:2500VA
Break Capacity DC Vmax: 300Vdc / Imax:5A / Pmax:150W
Binary Output (Semiconductor Type)
Quantity 4pairs
Type: Open-collector, Combination type male
Break Capacity DC 5~15Vdc / 5mA, 10mA max
Response time: 100us
Synchronization
Synchronization Mode   GPS, SMA type antenna connector
Power supply & Environment
Nominal Input Voltage 110V/220/230V ac, Appointed
Permissible Input Voltage 85~264Vac, 125~350VDC, auto-protective
Nominal Frequency 50/60Hz
Permissible Frequency 45Hz~65Hz
Power Consumption 1500 VA max
Connection Type Standard AC socket 60320
Operating Temperature -10℃~55℃
Storage Temperature -20℃~70℃
Humidity <95%RH, non-condensing
Others
PC Connection RJ45 Ethernet, 10/100M
Grounding Terminal 4mm banana socket
Weight 19.5 Kg
Dimensions(W x D x H) 360×450×140(mm) 
Additional Information (Optional Modules)
Energy Meter Calibration Hardware is ready, to be active
Sensor Usage Mechanical meters / Electronic meters
Sensor Output High lever:>4.5V, Low level:<0.2V
Pulse Input 1 pulse input port, 5Vdc high level valid only.
Pulse Range 500KHz pulse input Max.
Pulse Output 1 Transistor output, Open-collector, 5Vdc/5mA
Model Current Outputs Voltage Outputs Optional Function
K3066i 6×35A @ 450VA max
3×70A @ 850VA max
7×310V @ 90VA max ● Energy Meter Cal.
K3063i 6×35A @ 450VA max
3×70A @ 850VA max
4×310V @ 124VA max
K3030i 3×35A @ 450VA max 4×310V @ 124VA max